Active Electrical Distribution Network. Группа авторов

Читать онлайн книгу.

Active Electrical Distribution Network - Группа авторов


Скачать книгу
I*sbq, and I*scq). The addition of the quadrature component and in-phase component of the above-estimated reference signals provides the reference source currents (I*sa, I*sb, and I*sc). However, the hysteresis-based current controller is implemented for the generation of gating pulses for the DSTATCOM-BESS system [25–27].

      Figure 4.4 MATLAB simulation of indirect current control theory controlled for the DSTATCOM-BESS system.

      4.5 Results Analysis under a Balanced System

      The proposed system is analyzed under a balanced system condition that considers linear, nonlinear, and induction motor loads for demonstrating the performance on harmonic eliminations. The system is analyzed for source voltage (Vs), terminal voltage (Vt), source current (Is), compensating current (Ic), load currents (Il), battery voltage (Vbb), and battery current (Ibb) based signals. The parameters under the system consideration are as follows:

      Source: Vpeak = 415 V, 3-Phase, 50 Hz

      Linear load: Resistiveload = 1000 Ω, Inductiveload = 1e−3H

      Nonlinear load: Rectifier-based inductive load with Rload = 1000 Ω, Lload = 1e−3H

      Induction motor load: Nominal power = 3730VA, 415 V, 50 Hz and Tm = 10, hysteresis controller band 0.1

      Battery and controller parameter: VOC = 720 V, Rb1 = 0.1 Ω, Rb2 = 1000 Ω, Cb2 = 1688 F, Cdc = 5000 F, I*smd = 35

      PI controller: Proportional constant = 043, Integrator constant = 0.15

      Figure 4.5 Response of DSTATCOM-BESS under a balanced linear load.

      4.5.2 Response of DSTATCOM-BESS under a Nonlinear Load

      Figure 4.7 Source side frequency spectrum.

      4.5.3 Response of DSTATCOM-BESS under an Induction Motor (IM) Load

      Figure 4.9 Response of DSTATCOM-BESS under an induction motor load.

      Figure 4.10 Source side frequency spectrum.

      Figure 4.11 Load side frequency spectrum.

S. No. Type of load Indirect current control theory controlled DSTATCOM-BESS
Source side THD Load side THD
1 Linear load 0.57%
Скачать книгу