Smart Solar PV Inverters with Advanced Grid Support Functionalities. Rajiv K. Varma

Читать онлайн книгу.

Smart Solar PV Inverters with Advanced Grid Support Functionalities - Rajiv K. Varma


Скачать книгу
may be needed to avoid the adverse impacts of a conventional solar PV connection [21]. Such a dedicated feeder without any loads can be directly connected to the substation. It may be noted that such reconductoring or network upgrades are quite expensive and time consuming to implement.

      1.2.11 Change in Reactive Power Flow in Feeders

      Voltage variations due to active power generation by solar PV systems coupled with operation of voltage regulators and switching of capacitor banks leads to change in reactive power flow in the lines [53]. For instance, if a capacitor is switched off, reactive power earlier being supplied by the capacitor is no longer available and needs to be imported from neighboring lines or utilities. This may also have financial impacts on the distribution utilities that have a high import component of power from neighboring utilities.

      1.2.12 Line Losses

      Line I2R heating losses are proportional to the current flow in the feeders. If the solar PV systems partially offset the line loading the losses will decrease [54, 55]. It is shown on an AEP network that low to moderate level of solar PV penetration tends to lower the line losses since the power produced by the solar PV systems tends to offset the load, and consequently, the import of current from the grid source reduces [56]. However, if the solar PV systems cause a net increase in line current the losses will increase. In some cases, the line losses with solar PV systems may become higher than the case with no solar PV systems installed [21]. These losses require increased power import over the lines to supply the same load, increased heating in lines resulting in faster aging, and decrease in lifespan of line infrastructure.

      1.2.13 Harmonic Injections

      Solar PV systems inject harmonics into the grid which may increase the THD of the bus voltages [57]. Although individual solar PV inverters are certified to be harmonic compliant with existing Standards, such as [47, 58] harmonic injections from several inverters within a solar PV plant or multiple solar PV plants connected to a feeder system can get combined. The harmonics, however, do not add up in an arithmetic manner. Certain amount of harmonic cancellation occurs due to phase differences amongst the harmonics from different solar PV systems [57]. Solar PV systems connected to LV feeder systems tend to create more harmonic distortion than at higher voltage systems [59].

      Two types of harmonic sources exist in a power distribution system. One is the background harmonics in the grid while the other is the harmonic injections from the power electronic sources such as a wind generator plant, adjustable speed drive, PV inverters, and dynamic reactive power compensators (SVC or STATCOM), etc.

      In distribution systems, series resonance is characterized by minimum impedance values at the resonant frequencies. The ambient harmonic voltages in the grid drive high harmonic currents in the downstream network at these low impedances. This is the harmonic distortion problem caused by series resonance [60]. On the other hand, parallel resonance is exhibited due to high impedances at the resonant frequencies. The currents from the harmonic current sources (PV inverters, wind turbine generators, Adjustable Speed Drives, etc.) interact with these high impedances resulting in significantly high harmonic voltages in the network. This is the harmonic distortion problem caused by parallel resonance [60].

      Series and parallel resonance can either exist independently or coexist at the same location. These resonances are a characteristic of a specific power system. By themselves, they do not cause any adverse effect on the system. Just as it takes two hands to clap, i.e. only when there is an alignment of a network resonant frequency and a harmonic injection at the same frequency, a potential of adverse harmonic distortion can occur.

      Consider a distribution line with series inductance connected to a wind plant with a power factor correction capacitor. For the background harmonic voltages in the grid, the above inductor–capacitor combination presents a situation of series resonance. The background harmonic voltages see a low impedance path and inject high amount of harmonic currents resulting in substantial voltage distortion at the terminals of the wind plant. Meanwhile, the same inductor–capacitor combination appears as a parallel resonant circuit for the harmonic currents injected by the inverters in the wind plant. If the parallel resonance frequencies align with the harmonics injected by the wind plant, the harmonic currents from the wind plant see large impedance resulting in substantially high harmonic voltages at the wind plant terminals [60].

      The vertical bold arrow qualitatively depicts harmonic current injection Ih at the 11th harmonic (660 Hz). The bus voltage (pu) is also illustrated on the y‐axis. Three cases of frequency scan are depicted. Figure 1.14a,b illustrates the cases when the network resonant peak does not coincide with the injected 11th harmonic at 660 Hz. For both of these cases, the harmonic voltage (Vh = Ih × Zh) corresponding to the 11th harmonic current injection is not high. Figure 1.14c portrays the frequency scan when the network resonant frequency aligns with 11th harmonic (660 Hz) current injection. In this case, the injected harmonic sees very high impedance Zh. The corresponding harmonic voltage (Vh = Ih × Zh) becomes very high and may exceed the utility acceptable voltage limit (indicated by the horizontal dashed line) and potentially damage customer equipment.

      The above example is for one injected harmonic for one network resonance mode. However, in active power systems, there may be several network resonant frequencies and several harmonic current injections.

Schematic illustration of (a, b) Network resonant frequency not coincident with harmonic frequency. (c) Network resonant frequency coincident with 11th harmonic frequency (660 Hz).

      These


Скачать книгу