Intelligent Renewable Energy Systems. Группа авторов
Читать онлайн книгу.presented in Figure 1.5.
Table 1.6 Optimum placement of RDGs and shunt capacitors to the 33-bus distribution network.
Load hour | Optimum size of biomass DG (kW) | Optimum size of solar PV (kW) | Optimum size of shunt capacitor (kVAr) | Active power loss before placement of DG (kW) | Active power loss after placement of DG (kW) | Base VDI (before placement of DG) | VDI after placement of DG |
---|---|---|---|---|---|---|---|
Location – 14 | Location - 31 | Location - 30 | |||||
1 | 621.5083 | 1759.48 | 800 | 78.6548 | 29.4379 | 0.0453 | 0.0037 |
2 | 586.0025 | 1759.48 | 750 | 68.7376 | 25.8221 | 0.0396 | 0.0032 |
3 | 568.0646 | 1759.48 | 725 | 64.0501 | 24.1064 | 0.0369 | 0.003 |
4 | 550.005 | 1759.48 | 700 | 59.5413 | 22.4517 | 0.0343 | 0.0028 |
5 | 550.005 | 1759.48 | 700 | 59.5413 | 22.4517 | 0.0343 | 0.0028 |
6 | 568.0646 | 1759.48 | 725 | 64.0501 | 24.1064 | 0.0369 | 0.003 |
7 | 617.4665 | 1759.48 | 800 | 78.6548 | 28.7562 | 0.0453 | 0.0036 |
8 | 671.2714 | 1759.48 | 925 | 112.8660 | 31.2546 | 0.0651 | 0.0039 |
9 | 683.3 | 1759.48 | 1025 | 150.3564 | 30.2443 | 0.0868 | 0.0035 |
10 | 685.9 | 1759.48 | 1125 | 181.4934 | 31.9668 | 0.1048 | 0.0035 |
11 | 687.6 | 1759.48 | 1150 | 198.3321 | 33.0856 | 0.1146 | 0.0036 |
12 | 667.5 | 1759.48 | 1175 | 202.6771 | 32.981 | 0.1171 | 0.0033 |
13 | 661.5 | 1759.48 | 1150 | 198.3321 | 32.0711 | 0.1146 | 0.0032 |
14 | 683.7 | 1759.48 | 1175 | 202.6771 | 33.5922 | 0.1171 | 0.0035 |
15 | 730.9 | 1759.48 | 1175 | 202.6771 | 36.8247 | 0.1171 | 0.0043 |
16 | 752.1 | 1759.48 | 1175 | 189.8051 | 39.7576 | 0.1096 | 0.0048 |
17 | 812.9 | 1759.48 | 1175 | 185.6225 | 50 | 0.1072 | 0.0066 |
18 | 866.0 | 1759.48 | 1225 | 185.6225 | 63.9226 | 0.1072 | 0.0086 |
19 | 861.3 | 1759.48 | 1175 | 173.3949 | 63.4637 | 0.1001 | 0.0087 |
20 | 851.4 | 1759.48 | 1175 | 169.4248 | 62.2863 | 0.0978 | 0.0083 |
|